According to standards
Low-smoke halogen-free cable
Low-smoke halogen-free cable
Keywords:
temperature
cables
flame
Belonging Category:
Product Description
GB/T 19666-2019 "General specifications for flame-retardant and fire-resistant wires and cables" GB/T 12666-2008 "Test methods for combustion of wires and cables"
GB/T 18380-2022 "Combustion test"
GB/T 17651-2021 "Determination of smoke density of cables or optical cables burning under specified conditions"
GB/T 17650-2021 "Test methods for gases released during combustion of materials taken from cables or optical cables" GA 306-2007 "Flame-retardant and fire-resistant cables, plastic insulation, flame-retardant and fire-resistant cable grading and requirements"
Product model and name
Model | Name |
ZR- | Flame retardant type |
NH- | Fire resistant type |
WDZ- | Halogen-free low-smoke flame-retardant type |
WDZN- | Halogen-free low-smoke flame-retardant and fire-resistant type |
... | ... |
Note:
● Halogen-free characteristics: The cable will not release halogen element (F, CI, Br, I) compounds during use and accidental fire, that is, it will not release toxic gases.
● Low smoke: Under accidental fire conditions, even if ignited, the cable product will not release dense smoke, and is evaluated by light transmittance during the experiment.
● Flame retardant (ZR): Under flame conditions, the cable product only spreads locally and the flame extinguishes itself in a short time after the fire source is removed. The flame retardant levels are divided into A, B, C, and D.
● Fire resistant (NH): Under flame conditions (ordinary flame temperature 750°C~800°C, A-level flame temperature 950°C~1000°C), the cable product can operate normally for more than 90min.
● WDZ-type cables are divided into WDZA-, WDZB-, WDZC-, and WDZD- according to the flame retardant level. According to environmental requirements, they can also have fire-resistant properties, marked as WDZN-, and the corresponding flame retardant levels are WDZAN-, WDZBN-, WDZCN-, and WDZDN-. GA 306-2007 "Flame-retardant and fire-resistant cables, plastic insulation, flame-retardant and fire-resistant cable grading and requirements" specifies the following requirements for fire resistance levels:
Fire resistance level and technical requirements | ||||||
Fire resistance level | Technical requirements | |||||
Fire resistance characteristics | Smoke toxicity | Smoke density (minimum light transmittance) 1% | Corrosion resistance | |||
Test conditions | Line integrity | PH value | Conductivity μS/mm | |||
Class I | Fire temperature: 750°C~800°C | Meet GB/T | Comply with | ≥80 | ≥4.3 | ≤10 |
IA level | Fire temperature: 950°C~1000°C | |||||
Class II | Fire temperature: 750°C~800°C | ≥60 | ||||
IIA level | Fire temperature: 950°C~1000°C | |||||
Class III | Fire temperature: 750°C~800°C | Comply with | ≥20 | One | ||
IIIA level | Fire temperature: 950°C~1000°C | |||||
Class IV | Fire temperature: 750°C~800°C | One | One | |||
IVA level | Fire temperature: 950°C~1000°C | |||||